ME 322 • Unit 3 • Second Law Applications

Preclass 3.2 & Class Activity 3.2 Practice Suite

Interactive mastery suite covering heat engines, refrigerators, heat pumps, power plant logistics, food sensible refrigeration enthalpy (Table A-7), and HVAC life-cycle economic optimization.

📋 Key Concept & Formula Tables ✍️ Preclass 3.2 Quiz (Questions 1 – 6) ⚙️ In-Class Activity 3.2 Engineering Problems (Problems 7 – 10)
Completed: 0 / 10 Score: 0 / 19 pts

📋 Key Concept & Formula Matrix (Copy into Notes)

Governing relations strictly from the ME 322 Equation Sheet and Property Tables (6th Edition).

1. Thermal Cycles & Governing Performance Relations

Thermal Device Energy Balance (1st Law) Performance Metric Equation Sheet Formula Reversible (Carnot) Limit
Heat Engine (HE) $\dot{W}_{net} = \dot{Q}_H - \dot{Q}_L$ Thermal Efficiency $\eta_{th}$ $$\eta_{th} = \frac{\dot{W}_{net}}{\dot{Q}_H} = 1 - \frac{\dot{Q}_L}{\dot{Q}_H}$$ $$\eta_{th,C} = 1 - \frac{T_L}{T_H}$$
Refrigerator (R) $\dot{Q}_H = \dot{Q}_L + \dot{W}_{net,in}$ Cooling COP $\text{COP}_R$ $$\text{COP}_R = \frac{\dot{Q}_L}{\dot{W}_{net,in}} = \frac{\dot{Q}_L}{\dot{Q}_H - \dot{Q}_L}$$ $$\text{COP}_{R,C} = \frac{T_L}{T_H - T_L}$$
Heat Pump (HP) $\dot{Q}_H = \dot{Q}_L + \dot{W}_{net,in}$ Heating COP $\text{COP}_{HP}$ $$\text{COP}_{HP} = \frac{\dot{Q}_H}{\dot{W}_{net,in}} = \text{COP}_R + 1$$ $$\text{COP}_{HP,C} = \frac{T_H}{T_H - T_L}$$

2. Specialized Engineering Applications & Unit Conversions

Application Topic Governing Equation Property Lookup / Key Constant Units & Equation Sheet Conversion
Power Unit Conversion $$\dot{W}_{hp} = \frac{\dot{W}_{Btu/hr}}{2544.5}$$ ME 322 Equation Sheet Conversion Factors $$1\text{ hp} = 2544.5\text{ Btu/hr} = 0.7457\text{ kW}$$
Coal Furnace Combustion Logistics $$\dot{Q}_H = \dot{m}_{coal} \cdot HV$$
$$\dot{m}_{air} = AF \cdot \dot{m}_{coal}$$
Heating Value: $HV$ in $\text{kJ/kg}$
Gravimetric Air-Fuel Ratio: $AF$ in $\text{kg air/kg coal}$
$$1\text{ MW} = 1000\text{ kW} = 1000\text{ kJ/s}$$
$$1\text{ day} = 86,400\text{ s}$$
Food Sensible Refrigeration $$\Delta \dot{H} = \dot{m} \cdot c_p \cdot \Delta T$$
$$\dot{Q}_L = \Delta \dot{H}$$
Table A-7 (Food Properties):
Bananas above freezing ($-0.8^\circ\text{C}$):
$$c_p = 3.35\text{ kJ/kg}\cdot^\circ\text{C}$$
$$\dot{m}\text{ [kg/s]} = \frac{\text{kg/hr}}{3600}$$
$$\text{kW} = \text{kJ/s}$$
HVAC Life-Cycle Economics $$W_{in} = \frac{Q_{cooling}}{\text{COP}}$$
$$\text{Annual Cost} = W_{in} \times \text{Rate}$$
$$\text{Total}_{10\text{yr}} = \text{Capital} + 10(\text{Annual})$$
Electricity Rate (e.g. $\$0.10/\text{kWh}$)
Capital Equipment Cost
Payback Period:$$\text{Payback} = \frac{\Delta \text{Capital}}{\Delta \text{Annual Savings}}$$
Official Course Preparation

Part A: Preclass 3.2 Quiz Problems (Questions 1 – 6)

Problems 2 through 7 from the official Canvas Preclass 3.2 (ignoring the video study reflection prompt).

Question 1 (Preclass Q2) 1 Point • Heat Engine Net Power

If $15\text{ Btu/min}$ of heat are transferred to a heat engine, and $5\text{ Btu/min}$ are rejected to the environment, what is the net power output of the engine?

💡 Hint: Heat Engine First Law Balance
ME 322 Formula Sheet: Heat Engines

From the First Law energy balance for a closed cycle heat engine:
$$\dot{W}_{net,out} = \dot{Q}_H - \dot{Q}_L$$ where $\dot{Q}_H$ is the heat input from the high-temperature source and $\dot{Q}_L$ is the heat rejected to the low-temperature sink.

📝 Show Full Worked Solution

Step 1: Identify Given Values:

$$\dot{Q}_H = 15\text{ Btu/min}$$ $$\dot{Q}_L = 5\text{ Btu/min}$$

Step 2: Apply Energy Balance:

$$\dot{W}_{net,out} = \dot{Q}_H - \dot{Q}_L = 15\text{ Btu/min} - 5\text{ Btu/min} = 10\text{ Btu/min}$$
Correct Answer: 10 Btu/min (Option B)
Question 2 (Preclass Q3) 1 Point • Thermal Efficiency

What is the thermal efficiency of the heat engine in the previous problem?

💡 Hint: Thermal Efficiency Definition
ME 322 Formula Sheet: Thermal Efficiency

Thermal efficiency is defined as the net work output divided by the total heat input:
$$\eta_{th} = \frac{\dot{W}_{net}}{\dot{Q}_H} = 1 - \frac{\dot{Q}_L}{\dot{Q}_H}$$

📝 Show Full Worked Solution

Step 1: Apply Thermal Efficiency Formula:

$$\eta_{th} = \frac{\dot{W}_{net}}{\dot{Q}_H} = \frac{10\text{ Btu/min}}{15\text{ Btu/min}} = \frac{2}{3} \approx 0.6667$$

Rounding to two decimal places yields $0.66$ (or $66.7\%$).

Correct Answer: 0.66 (Option D)
Question 3 (Preclass Q4) 1 Point • Refrigerator Heat Balance

A refrigerator that provides $5\text{ kW}$ of cooling is powered by a $2\text{ kW}$ compressor. What is the heat rejection rate from the refrigerator?

💡 Hint: Refrigerator Energy Accounting
ME 322 Formula Sheet: Refrigerators

For a refrigeration cycle, the heat rejected to the warm surroundings ($\dot{Q}_H$) must balance all energy inputs into the refrigerant:
$$\dot{Q}_H = \dot{Q}_L + \dot{W}_{in}$$

📝 Show Full Worked Solution

Step 1: Identify Energy Streams:

$$\dot{Q}_L = 5\text{ kW}\text{ (cooling load extracted from refrigerated space)}$$ $$\dot{W}_{in} = 2\text{ kW}\text{ (electric power input to compressor)}$$

Step 2: Solve for Total Heat Rejected:

$$\dot{Q}_H = \dot{Q}_L + \dot{W}_{in} = 5\text{ kW} + 2\text{ kW} = 7\text{ kW}$$
Correct Answer: 7 kW (Option C)
Question 4 (Preclass Q5) 1 Point • Refrigerator COP

What is the Coefficient of Performance ($\text{COP}_R$) of the refrigerator in the previous problem?

💡 Hint: Definition of COP for Refrigeration
ME 322 Formula Sheet: Refrigerator COP

The COP of a refrigerator is defined as the desired cooling effect divided by the required work input:
$$\text{COP}_R = \frac{\dot{Q}_L}{\dot{W}_{net,in}}$$

📝 Show Full Worked Solution

Step 1: Compute COP:

$$\text{COP}_R = \frac{\dot{Q}_L}{\dot{W}_{in}} = \frac{5\text{ kW}}{2\text{ kW}} = 2.5$$
Correct Answer: 2.5 (Option D)
Question 5 (Preclass Q6) 1 Point • Heat Engine Heat Rejection

A heat engine has an efficiency of $30\%$ and a rated power output of $5\text{ MW}$. The rate heat is being rejected from the engine is closest to?

💡 Hint: Two-Step Heat Engine Accounting
ME 322 Formula Sheet: Efficiency & Balance

1. Solve for total heat input: $\dot{Q}_H = \frac{\dot{W}_{net}}{\eta_{th}}$
2. Solve for heat rejected: $\dot{Q}_L = \dot{Q}_H - \dot{W}_{net}$

📝 Show Full Worked Solution

Step 1: Calculate Heat Input Rate $\dot{Q}_H$:

$$\dot{Q}_H = \frac{\dot{W}_{net}}{\eta_{th}} = \frac{5\text{ MW}}{0.30} = 16.667\text{ MW}$$

Step 2: Calculate Heat Rejection Rate $\dot{Q}_L$:

$$\dot{Q}_L = \dot{Q}_H - \dot{W}_{net} = 16.667\text{ MW} - 5.0\text{ MW} = 11.667\text{ MW}$$

The closest listed option is $12\text{ MW}$.

Correct Answer: 12 MW (Option B)
Question 6 (Preclass Q7) 1 Point • Reversible Dual-Mode Heat Pump

Heat pumps are often designed as reversible systems: they can provide heating in cold weather and cooling (air conditioning) in warm weather. If the Coefficient of Performance for a $10,000\text{ Btu/hr}$ heat pump when acting as a heat pump is $4.0$, what is its COP when acting as an air conditioner?

💡 Hint: Relationship Between COP_HP and COP_R
ME 322 Formula Sheet: HP & Ref Identity

From the ME 322 Equation Sheet:
$$\text{COP}_{HP} = \text{COP}_R + 1$$ Note: An air conditioner is thermodynamically identical to a refrigerator (both cool the low-temperature space $\dot{Q}_L$). Thus $\text{COP}_{AC} = \text{COP}_R$.

📝 Show Full Worked Solution

Step 1: Apply the HP-Refrigeration Identity:

$$\text{COP}_{HP} = \frac{\dot{Q}_H}{\dot{W}_{in}} = \frac{\dot{Q}_L + \dot{W}_{in}}{\dot{W}_{in}} = \frac{\dot{Q}_L}{\dot{W}_{in}} + 1 = \text{COP}_R + 1$$

Step 2: Solve for Cooling COP:

$$\text{COP}_{AC} = \text{COP}_R = \text{COP}_{HP} - 1 = 4.0 - 1.0 = 3.0$$
Correct Answer: 3.0 (Option A)
Collaborative Engineering Teamwork

Part B: Class Activity 3.2 Short Answer Problems (Problems 7 – 10)

Multi-step engineering calculations directly from the in-class problem set with interactive numerical validation and full step-by-step solutions.

Problem 7 (Activity Question 1) 2 Points • Heat Engine Power Output & HP Conversion

A heat engine has a heat input of $30,000\text{ Btu/hr}$ and a thermal efficiency of $40\%$. How much net power will this engine produce?

Heat Engine Schematic
Figure: Heat Engine schematic receiving heat from high-temperature source and rejecting to low-temperature sink.
Part (a): Net power output in $\text{Btu/hr}$
Btu/hr
Part (b): Net power output in Horsepower ($\text{hp}$)
hp
💡 Hint: Efficiency & Horsepower Conversion Factor
ME 322 Formula Sheet: Conversion Factors

1. Power in Btu/hr: $\dot{W}_{net} = \eta_{th} \times \dot{Q}_H$
2. Horsepower conversion from ME 322 Equation Sheet:
$$1\text{ hp} = 2544.5\text{ Btu/hr}$$ $$\dot{W}_{hp} = \frac{\dot{W}_{Btu/hr}}{2544.5\text{ Btu/hp}\cdot\text{hr}}$$

📝 Show Full Worked Solution

Part (a): Calculate Power Output in Btu/hr:

$$\dot{W}_{net} = \eta_{th} \cdot \dot{Q}_H = 0.40 \times 30,000\text{ Btu/hr} = 12,000\text{ Btu/hr}$$
Answer (a): 12,000 Btu/hr

Part (b): Convert to Horsepower:

$$\dot{W}_{net} = \frac{12,000\text{ Btu/hr}}{2544.5\text{ Btu/hp}\cdot\text{hr}} = 4.716\text{ hp} \approx 4.72\text{ hp}$$
Answer (b): 4.72 hp
Problem 8 (Activity Question 2) 4 Points • Coal Power Plant Logistics & Air Flow

A coal-burning steam power plant produces a net power of $\dot{W}_{net} = 300\text{ MW}$ with an overall thermal efficiency of $\eta_{th} = 32\%$. The heating value ($HV$) of the coal is $28,000\text{ kJ/kg}$, a standard train car carries approximately $105,000\text{ kg}$ of coal, and the gravimetric air-fuel ratio in the furnace is $12\text{ kg air / kg coal}$.

Part (a): Total thermal heating load ($\dot{Q}_H$) needed to run the facility:
MW
Part (b): Total mass of coal consumed during a 24-hour operating period:
kg/day (e.g. 2.89e6 or 2892857)
Part (c): Number of train cars of coal that must arrive at the plant each day:
cars/day
Part (d): Mass flow rate of combustion air ($\dot{m}_{air}$) through the furnace:
kg/s
💡 Hint: Step-by-Step Logistics & Rate Accounting
ME 322 Combustion & Unit Balances

1. Heating Load: $\dot{Q}_H = \frac{\dot{W}_{net}}{\eta_{th}}$ (with $\text{MW} = 1000\text{ kJ/s}$)
2. Daily Energy & Coal Mass: $Q_{H,24hr} = \dot{Q}_H \times (24 \times 3600\text{ s})$. Then $m_{coal} = \frac{Q_{H,24hr}}{HV}$.
3. Train Cars: $\text{Cars/day} = \frac{m_{coal}}{105,000\text{ kg/car}}$.
4. Air Mass Flow: Coal flow rate is $\dot{m}_{coal} = \frac{\dot{Q}_H}{HV}$. Then $\dot{m}_{air} = AF \times \dot{m}_{coal}$.

📝 Show Full Worked Solution

Part (a): Thermal Heating Load $\dot{Q}_H$:

$$\dot{Q}_H = \frac{\dot{W}_{net}}{\eta_{th}} = \frac{300\text{ MW}}{0.32} = 937.5\text{ MW} = 937,500\text{ kJ/s}$$
Answer (a): 937.5 MW

Part (b): Mass of Coal Consumed in 24 Hours:

$$\Delta t = 24\text{ hr} \times 3600\text{ s/hr} = 86,400\text{ s}$$ $$Q_H = \dot{Q}_H \cdot \Delta t = 937,500\text{ kJ/s} \times 86,400\text{ s} = 8.10 \times 10^{10}\text{ kJ}$$ $$m_{coal} = \frac{Q_H}{HV} = \frac{8.10 \times 10^{10}\text{ kJ}}{28,000\text{ kJ/kg}} = 2,892,857\text{ kg/day} \approx 2.89 \times 10^6\text{ kg/day}$$
Answer (b): 2.89 × 10⁶ kg/day (2,892,857 kg)

Part (c): Daily Train Cars Required:

$$\text{Number of train cars} = \frac{2,892,857\text{ kg/day}}{105,000\text{ kg/car}} = 27.55 \approx 28\text{ cars/day}$$
Answer (c): 28 cars/day

Part (d): Air Mass Flow Rate $\dot{m}_{air}$:

$$\dot{m}_{coal} = \frac{\dot{Q}_H}{HV} = \frac{937,500\text{ kJ/s}}{28,000\text{ kJ/kg}} = 33.482\text{ kg/s}$$ $$\dot{m}_{air} = AF \times \dot{m}_{coal} = 12\text{ kg air/kg coal} \times 33.482\text{ kg coal/s} = 401.785\text{ kg/s} \approx 402\text{ kg/s}$$
Answer (d): 402 kg/s
Problem 9 (Activity Question 3) 4 Points • Banana Refrigeration & Property Table Lookup

Bananas are to be cooled from $24^\circ\text{C}$ to $13^\circ\text{C}$ at a mass rate of $215\text{ kg/hr}$ by a refrigeration system. The electric power input to the refrigerator compressor is $1.4\text{ kW}$.

Part (a): Rate of enthalpy change ($\Delta \dot{H}$) of the bananas necessary to achieve this temperature drop:
kW
Part (b): The refrigerator's cooling rate ($\dot{Q}_L$):
kJ/s
Part (c): The Coefficient of Performance ($\text{COP}_R$) of the refrigerator:
dimensionless
Part (d): Rate of heat rejected to the kitchen environment ($\dot{Q}_H$):
kW (or kJ/s)
💡 Hint: Property Table Lookup (Table A-7) & Sensible Cooling
Property Tables: Table A-7 (Food Properties)

1. In Table A-7, locate Bananas:
Freezing point is $-0.8^\circ\text{C}$. Since $24^\circ\text{C} \to 13^\circ\text{C}$ is above freezing, read:
$$c_p = 3.35\text{ kJ/kg}\cdot^\circ\text{C}$$ 2. Convert mass flow rate to $\text{kg/s}$: $\dot{m} = \frac{215\text{ kg/hr}}{3600\text{ s/hr}}$.
3. $\Delta \dot{H} = \dot{m} \cdot c_p \cdot \Delta T$.
4. Cooling rate $\dot{Q}_L = \Delta \dot{H}$, $\text{COP}_R = \frac{\dot{Q}_L}{\dot{W}_{in}}$, and $\dot{Q}_H = \dot{Q}_L + \dot{W}_{in}$.

📝 Show Full Worked Solution

Property Table Lookup:
From Property Tables (6th Edition) Table A-7: Properties of foods:
For bananas above freezing: $c_p = 3.35\text{ kJ/kg}\cdot\text{K}$.

Part (a): Enthalpy Change Rate $\Delta \dot{H}$:

$$\dot{m} = \frac{215\text{ kg/hr}}{3600\text{ s/hr}} = 0.05972\text{ kg/s}$$ $$\Delta T = 24^\circ\text{C} - 13^\circ\text{C} = 11^\circ\text{C} = 11\text{ K}$$ $$\Delta \dot{H} = \dot{m} c_p \Delta T = (0.05972\text{ kg/s})(3.35\text{ kJ/kg}\cdot\text{K})(11\text{ K}) = 2.2007\text{ kJ/s} = 2.20\text{ kW}$$
Answer (a): 2.20 kW

Part (b): Cooling Rate $\dot{Q}_L$:

$$\dot{Q}_L = \Delta \dot{H} = 2.20\text{ kJ/s}$$
Answer (b): 2.20 kJ/s (or 2.2 kW)

Part (c): Refrigerator COP:

$$\text{COP}_R = \frac{\dot{Q}_L}{\dot{W}_{in}} = \frac{2.2007\text{ kW}}{1.4\text{ kW}} = 1.5719 \approx 1.57$$
Answer (c): 1.57

Part (d): Heat Rejected to Environment $\dot{Q}_H$:

$$\dot{Q}_H = \dot{Q}_L + \dot{W}_{in} = 2.2007\text{ kW} + 1.4\text{ kW} = 3.6007\text{ kW} \approx 3.60\text{ kW}$$
Answer (d): 3.60 kW (or 3.6 kJ/s)
Problem 10 (Activity Question 4) 3 Points • HVAC Life-Cycle Economics & Capital Payback

Consider a commercial building whose annual air conditioning cooling load is estimated to be $120,000\text{ kWh/year}$ in a region where the unit cost of electricity is $\$0.10/\text{kWh}$. Two air conditioning units are being evaluated for purchase over a $10\text{-year}$ expected operating life:

  • Air Conditioner A: Seasonal average $\text{COP} = 3.2$, Initial capital cost = $\$5,000$.
  • Air Conditioner B: Seasonal average $\text{COP} = 5.0$, Initial capital cost = $\$8,000$.
Building Air Conditioning Comparison Schematic
Figure: Building cooling comparison between Unit A and higher-efficiency Unit B (use numerical values in problem text).
Part (a): What is the annual operating electricity cost for each unit?
Part (b): What is the 10-year total life-cycle cost (Capital Cost + 10 Years Operating Cost) for each unit?
Part (c): Which air conditioner do you recommend purchasing, and what is the 10-year total cost savings?
💡 Hint: Life-Cycle Energy & Cost Equations
Engineering Economics: Life-Cycle Costing

1. Annual Electricity Needed: $W_{electric} = \frac{Q_{load}}{\text{COP}}$ in $\text{kWh/year}$.
2. Annual Cost: $\text{Cost/yr} = W_{electric} \times \$0.10/\text{kWh}$.
3. 10-Year Total: $\text{Total} = \text{Initial Cost} + 10 \times (\text{Annual Cost})$.
4. Savings: $\text{Savings} = \text{Total}_A - \text{Total}_B$.

📝 Show Full Worked Solution

Part (a): Annual Operating Cost:

For Unit A ($\text{COP} = 3.2$):

$$W_{in,A} = \frac{120,000\text{ kWh/yr}}{3.2} = 37,500\text{ kWh/year}$$ $$\text{Operating Cost}_A = 37,500\text{ kWh/yr} \times \$0.10/\text{kWh} = \$3,750/\text{year}$$

For Unit B ($\text{COP} = 5.0$):

$$W_{in,B} = \frac{120,000\text{ kWh/yr}}{5.0} = 24,000\text{ kWh/year}$$ $$\text{Operating Cost}_B = 24,000\text{ kWh/yr} \times \$0.10/\text{kWh} = \$2,400/\text{year}$$
Answer (a): Unit A: $3,750/yr; Unit B: $2,400/yr (Option A)

Part (b): 10-Year Life-Cycle Total Cost:

$$\text{Total Cost}_A = \$5,000 + 10(\text{\$3,750}) = \$5,000 + \$37,500 = \$42,500$$ $$\text{Total Cost}_B = \$8,000 + 10(\text{\$2,400}) = \$8,000 + \$24,000 = \$32,000$$
Answer (b): Unit A: $42,500; Unit B: $32,000 (Option B)

Part (c): 10-Year Savings & Recommendation:

$$\text{Total 10-Year Savings} = \$42,500 - \$32,000 = \$10,500$$ $$\text{Annual Savings} = \$3,750 - \$2,400 = \$1,350/\text{year}$$ $$\text{Payback Period} = \frac{\Delta \text{Initial Cost}}{\text{Annual Savings}} = \frac{\$8,000 - \$5,000}{\$1,350/\text{year}} = \frac{\$3,000}{\$1,350} = 2.22\text{ years}$$

Conclusion: Recommend purchasing Unit B. The $\$3,000$ higher initial investment is fully recouped in just $2.2$ years, yielding a net savings of $\$10,500$ over the equipment life.

Answer (c): Recommend Unit B (Saves $10,500) (Option B)